Three-phase power: wye, delta, and √3
CERT 3 · Commercial & Industrial Systems · ~12 min
Commercial power arrives as three sine waves offset 120° from each other. In a wye (star) connection the three phases share a neutral point: phase-to-neutral voltage × √3 = phase-to-phase voltage. That is where the two workhorse systems come from — 120/208 V (120 × 1.732 ≈ 208) and 277/480 V (277 × 1.732 ≈ 480).
Delta connections have no neutral by default; the three windings form a triangle and phase-to-phase is the only voltage. Motors love delta; lighting panels love wye.
Three-phase power is P = √3 × V_L × I_L × PF. Rearranged for current — I = P ÷ (√3 × V × PF) — it is the single most-used commercial exam formula: sizing feeders, breakers, and transformer secondaries all start here.
Exam focus: recognize the system from the voltages given, apply √3 in the correct direction (÷ to get phase-to-neutral, × to get line), and drill the power formula both ways.
Quiz — 3 questions
1. The phase-to-neutral voltage of a 480 V wye system is:
2. Line current for a 50 kW, 208 V three-phase load at PF 1.0 (nearest):
3. The three phases of a 3φ system are separated by: