UNIT 2.6 — LAYOUT

Receptacle placement and required circuits

CERT 2 · Residential Wiring · ~10 min

Community content — not verified by a licensed electrician. Lessons and questions here are written for study practice and pinned to NEC 2023. Code editions and local amendments vary by jurisdiction. Always confirm against your adopted code book and your licensing board's published exam outline before test day.

Dwelling receptacle spacing follows the 6/12 rule: no point along a wall line may be more than 6 feet from a receptacle, which in practice means one every 12 feet. Any wall section 2 feet or wider counts as wall space that must be served — including fixed panels of sliding doors and freestanding railings.

Kitchen countertops have their own tighter rule: no point along the counter wall line more than 24 inches from a receptacle, and any counter space 12 inches or wider must have one. These outlets are served by the two (minimum) 20 A small-appliance branch circuits from Unit 2.3 — and those circuits may not feed anything outside the kitchen, pantry, dining, and breakfast areas.

Certain loads demand dedicated individual branch circuits: the laundry (20 A), the bathroom receptacles (20 A, and this circuit serves bathrooms only), plus fixed appliances like dishwashers, disposals, and electric ranges per their nameplate.

Exam focus: 6/12 for general walls, 24 inches for countertops, 2-foot wall minimum, and which circuits are prohibited from serving other rooms. These are pure recall — free points once memorized.

General walls
6 ft / 12 ft rule
Countertops
Max 24 in from outlet
Wall counts if
≥ 2 ft wide
Knowledge check

Quiz — 3 questions

1. Along a dwelling wall, the maximum distance from any point to a receptacle is:

2. Kitchen countertop receptacles must be placed so no point is more than:

3. The 20 A bathroom receptacle circuit may also serve:

← SyllabusNext: Cable types and wiring methods →